BestBoilerHeader.gif



5C-SERIES BOILER MODEL

Boiler_Drawing.gif

Boiler Model/Size

5C-80

5C-90

5C-100

5C-125

5C-150

5C-175

5C-200

5C-250

5C-300

Gross Output Horsepower

H.P.

80

90

100

125

150

175

200

250

300

Steam Radiation

SQ. FT.

11,200 12,600 14,000 17,500 21,000 24,500 28,000 35,000 42,000
Steam Thermal

MBH

2,678 3,013 3,348 4,184 5,021 5,858 6,695 8,368 10,042
Steam per hr. 212 °F

LB/HR

2,760 3,105 3,450 4,312 5,175 6,037 6,900 8,625 10,350
Net Rating Steam Radiation

SQ. FT.

8,663 9,747 10,831 13,535 16,243 18,950 21,658 27,074 32,488
Steam Thermal

MBH

2,079 2,339 2,600 3,248 3,898 4,548 5,198 6,498 7,796
Firing Rate Oil

GPH

23.4 26.3 29.2 36.5 43.8 51.1 58.5 73.1 87.7
Gas

MBH

3,227 3,630 4,034 5,041 6,049 7,058 8,066 10,082 12,099
Heating Surface (Fireside)

SQ. FT.

400 450 500 625 750 875 1000 1250 1.500
Furnace Volume

CU. FT.

61.10 67.02 72.86 87.58 102.48 117.38 132.20 161.73 162.81

Boiler Model/Size

5C-80

5C-90

5C-100

5C-125

5C-150

5C-175

5C-200

5C-250

5C-300

A

Overall Length

FT.-IN.

8-6 9-2 1/4 9-10 3/8 11-9 7/8 13-6 5/8 15-3 1/2 16-11 7/8 20-9 21-4 1/4

B

Overall Width

IN.

77 77 77 77 77 77 77 77 77

C

Overall Height

IN.

87 87 87 87 87 87 87 87 87

D

Shell Length

FT.-IN.

6-0 6-8 1/4 7-4 3/8 9-0 7/8 10-9 5/8 12-6 1/2 14-2 7/8 17-8 18-0 1/4

E

Furnace Diameter

IN.

40 1/2 40 1/2 40 1/2 40 1/2 40 1/2 40 1/2 40 1/2 40 1/2 40 1/2

F

Furnace Length

IN.

64 3/8 72 5/8 80 3/4 101 1/4 122 142 3/4 163 1/4 204 1/2 208 1/2

G

Normal Water Line

IN.

75 3/8

75 3/8 75 3/8 75 3/8 75 3/8 75 3/8 75 3/8 75 3/8 75 3/8

H

Height (C.L. of Furnace)

IN.

36 1/4

36 1/4 36 1/4 36 1/4 36 1/4 36 1/4 36 1/4 36 1/4 36 1/4

J

Depth (Reversing Chamber)

IN.

10

10

10

10

10

10

10

10

10

K

Depth (Smoke Hood)

IN.

20

20 20 23 23 23 23 27 30

L

Vent Outlet Diameter

IN.

14

16 16 18 20 20 20 20/24 27

M

Top (Reversing Chamber)

IN.

72 5/8

72 5/8

72 5/8

72 5/8

72 5/8

72 5/8

72 5/8

72 5/8

72 5/8

P

Bottom (Reversing Chamber)

IN.

35

35

35

35

35

35

35

35

35

Q

Top (Smoke Hood)

IN.

83 3/4

83 3/4

83 3/4

83 3/4

83 3/4

83 3/4

83 3/4

83 3/4

83 3/4

R

Bottom (Smoke Hood)

IN.

60 5/8

60 5/8

60 5/8

60 5/8

60 5/8

60 5/8

60 5/8

60 5/8

60 5/8

S

Saddle Width

IN.

7

7

7

7

7

7

7

7

7

T

Saddle Length

IN.

61

61 61 61 61 61 61 61 61

V

C.L. (Front Saddle)

IN.

12

12

12

12

12

12

12

12

12

W

C.L. (Rear Saddle)

IN.

47 55 63 84 105 125 146 187 190
  Steam Outlet Size

IN.

6

8

8

8

8

8

8

8

10

  Return Size

IN.

3

3

3

3

3

3

3

3

4

Boiler Model/Size

5C-80

5C-90

5C-100

5C-125

5C-150

5C-175

5C-200

5C-250

5C-300

  Dry Weight (Approx.)

LBS.

7,689 8,904 9,479 10,993 12,394 13,864 15,317 18,232 21,140
  Operating Weight (Approx.)

LBS.

13,361 15,280 16,551 19,757 22,998 26,232 29,437 35,872 41,600


UL.gif NYserda.gif H-Stamp.gif R-Stamp.gif NB-Stamp.gif 2402 NEPTUNE AVENUE - BROOKLYN - NEW YORK - 11224
PHONE: (718) 372-4210      FAX: (718) 372-0255
UL: 2106 NYSERDA Approved Heating Boilers Repairs National Board

Copyright © 1998 Phoenix Energy Management, Inc.